How to Calculate Voltage Drop

A long wire run quietly loses voltage along the way. You won’t see it on paper, but you’ll notice it in the real world: lights that look dim at the far end of a workshop, a motor that runs hot, or a pump that struggles to start. The longer the wire and the heavier the load, the bigger the loss.

Here’s how to calculate voltage drop with a simple formula, plus a worked example you can follow with your own numbers. To skip the arithmetic, use the voltage drop calculator.

Panel120 VLoad20 A, ~112 V100 ft one way (12 AWG copper)Lost along the wire: 7.9 V (6.6%)
Voltage drop on a 100 ft run of 12 AWG copper at 20 A is about 7.9 V, or 6.6% of 120 V.

What voltage drop actually is

Every wire has a small amount of resistance. When current flows, that resistance eats a little of the voltage, so the load at the end of the wire receives less than what left the panel. The loss turns into a bit of heat in the wire.

Voltage drop is usually described as a percentage of the supply voltage. The National Electrical Code includes a recommendation (not a hard rule) of keeping a branch circuit under about 3%, and the whole run from the service to the farthest outlet under about 5%. Many designers use those numbers as a practical target.

The formula

For a single-phase circuit with copper wire, a common version is:

Voltage drop = 2 × K × I × L ÷ CM

  • K is a constant for the wire material. About 12.9 for copper and 21.2 for aluminum (these are typical values at normal operating temperature).
  • I is the current in amps. Use the actual load current, not the breaker size.
  • L is the one-way length of the run in feet. The “2” in the formula covers the trip out and back.
  • CM is the wire’s size in circular mils.

Typical circular mil values for common copper sizes: 12 AWG is 6,530 CM, 10 AWG is 10,380 CM, and 8 AWG is 16,510 CM.

Worked example: a 20 amp load, 100 feet away, on a 120 volt circuit

Say you’re running power to a workshop 100 feet from the panel and the load pulls 20 amps. Try 12 AWG copper first:

2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 volts

7.9 ÷ 120 = 6.6% drop. That’s well above the 3% target. Move up a size to 10 AWG:

2 × 12.9 × 20 × 100 ÷ 10,380 = 4.97 volts, or 4.1%

Better, but still over 3%. Try 8 AWG:

2 × 12.9 × 20 × 100 ÷ 16,510 = 3.13 volts, or 2.6%

Wire size (copper)Voltage dropPercent of 120 VUnder 3%?
12 AWG7.9 V6.6%No
10 AWG4.97 V4.1%No
8 AWG3.13 V2.6%Yes

So for this run, 8 AWG gets you under the target. The standard wire size for a 20 amp circuit is 12 AWG, which is correct for the breaker. But on a long run, voltage drop can call for bigger wire than the breaker alone would require. These are two separate checks, and you need to pass both.

What if the circuit is 240 volts?

The same drop in volts is a smaller percentage on a higher voltage. The 7.9 volts you lose with 12 AWG on the example above would be 7.9 ÷ 240 = 3.3% on a 240 volt circuit, which is much closer to the target. This is one reason long runs to outbuildings, pumps and big tools often use 240 volts.

When voltage drop matters most

  • Long runs to a garage, barn, shed or well pump.
  • Motors and compressors, which draw a lot of current when they start.
  • Low-voltage systems like 12 volt lighting or solar, where a loss of a single volt is a big percentage.
  • Heavy loads run close to the circuit’s rating for hours at a time.

How to reduce voltage drop

  1. Use a larger wire size. This is the usual fix.
  2. Shorten the run, if the layout allows it.
  3. Raise the system voltage, for example by running 240 V instead of 120 V.
  4. Reduce the load on that circuit.
  5. Use copper instead of aluminum, which has higher resistance for the same size.

Common mistakes

  • Using the total wire length instead of the one-way length. The formula already doubles it.
  • Using the breaker size instead of the real load current. A 20 amp breaker doesn’t mean the load draws 20 amps. Use the actual figure, or the continuous rating if the load runs for hours.
  • Treating voltage drop and ampacity as the same thing. Ampacity is how much current a wire can carry safely. Voltage drop is about performance over distance. Check both.
  • Ignoring temperature and conduit effects. Real-world values shift a little with heat, so leave some margin.
  • For more on how current, voltage and resistance relate, see our Ohm’s law calculator.

    Related guides

    See all construction and home project guides

    This guide gives general estimates for planning. Materials, local codes and site conditions vary, so confirm the details for your project with a local supplier or professional.