Voltage drop calculator

Use this voltage drop calculator to see how many volts you lose over a wire run. It works as a wire size voltage drop calculator too, so you can test different gauges and find the longest run within your limit.

⚡ Voltage Drop Calculator

Calculate voltage drop, or find the max wire length to stay within limits

Calculate Drop
Max Wire Length

How This Voltage Drop Calculator Works

“Calculate Drop” tells you how many volts you’ll lose over a known wire run. “Max Wire Length” works backward — tell it your target maximum drop percentage, and it solves for the longest wire run that stays within that limit.

The Formulas Used

  • Voltage Drop: Drop = 2 × (ohms/ft for gauge) × Length × Current ÷ 1000 (the “2×” accounts for the round trip of the circuit)
  • Max Length: Length = (Max Drop Voltage) ÷ (2 × ohms/ft × Current), where Max Drop Voltage = Supply Voltage × (Max Drop % ÷ 100)

NEC Recommended Limits

Circuit TypeRecommended Max Drop
Branch circuits (general)3%
Feeders2%
Combined (feeder + branch)5%

Frequently Asked Questions

Why does voltage drop matter?
Excessive voltage drop causes motors to run hotter and less efficiently, lights to dim, and electronics to behave erratically. It also wastes energy as heat in the wire itself.
What’s the easiest fix for high voltage drop?
Upgrading to a thicker (lower AWG number) wire gauge is the most common fix, since resistance per foot drops significantly with each gauge size increase. Shortening the run, where possible, also helps.
Is this calculator accurate enough for a real installation?
It uses standard copper wire resistance values and is a solid planning estimate. For code-compliance on a real job, always verify against NEC tables or consult a licensed electrician, since factors like conduit fill and temperature can affect actual resistance.